THÔNG SỐ KỸ THUẬT:
| MODEL | RML120/12 | RML072/12 | RML036/12 | |
| Power module | PML12 (12kVA) | |||
| INPUT | ||||
| Phase | 3 Phase + Neutral + Ground, 200V/208V/220V (line to line) | |||
| Voltage range | 166-261Vac (line-line), full load; | |||
| 166-125Vac (line-line), load derated from 100%-75% linearly | ||||
| Frequency range | 40Hz-70Hz | |||
| Power factor | >0.99 | |||
| THDi | THDi<3% @ 100% linear load | |||
| OUTPUT | ||||
| Voltage | 200V/208V/220V | |||
| Voltage regulation | 1.50% | |||
| Power factor | 0.8 | |||
| THDu | THD<1% (linear load), THD<5.5% (non-linear load) | |||
| Crest factor | 3:01 | |||
| Overload capability | 110% for 1 hour; 125% for 10 min; 150% for 1 min; >150% for 200ms | |||
| BATTERY | ||||
| Voltage | ±120VDC | |||
| Charge power | 20%*System Power | |||
| Charge voltage precision | ±1% | |||
| SYSTEM | ||||
| System efficiency | Normal mode:>92%; ECO mode:>98%; Battery mode:>92% | |||
| Display | LCD+LED, Touch Screen +Keyboard | |||
| IP class | IP20 | |||
| Interface | Standard: RS232, RS485, Dry contacts; Optional: SNMP | |||
| Operation/Storage temperature | 0-40℃/-40-70℃ | |||
| Relative humidity | 0-95% (non-condensing) | |||
| Noise | 55dB @ (1 meter away) | |||
| PHYSICAL | ||||
| Weight (kg) | Cabinet | 179 | 145 | 105 |
| Power Module | 22 | |||
| Dimension (W*D*H) | Cabinet | 600*900*2000 | 600*900*1600 | 600*900*1100 |
| (mm) | Power Module | 440*590*134 | ||