THÔNG SỐ KỸ THUẬT:
ITYS ES – UPS | |||
Sn | 1000 VA | 2000 VA | 3000 VA |
Pn | 800 W | 1600 W | 2400 W |
Input / output | 1-Jan | ||
Input | |||
Rated voltage | 230 V (110÷300 V) | ||
Rated frequency | 50/60 Hz | ||
Power factor | 0.98 | ||
Output | |||
Rated voltage | 208 / 220 / 230 / 240 V (± 2 %) | ||
Rated frequency | 50 / 60 Hz (45÷55 Hz / 54÷66 Hz) | ||
Overload | up to 150 % for 10 seconds | ||
Crest factor | 3:01 | ||
Connections | 3 x IEC 320 | 6 x IEC 320 | 4 x IEC 320 |
(C13) | (C13) | (C13) + terminals | |
Batteries | |||
Type | sealed lead-acid maintenance free – expected lifetime 3-5 years | ||
Back-up time at 75% of the rated load(1) | 10 min | 17 min | 9 min |
Sized for a back-up time of | 115 min @ 50 W | 154 min @ 100 W | 216 min @ 150 W |
Back-up time(2) + switching back on | 60 min @ 50 W | 60 min @ 100 W | 60 min @ 150 W |
Battery test | • | • | • |
Communication | |||
Interfaces | RS232 – USB | ||
Ethernet adapter | NET VISION (TCP / IP & SNMP) optional card | ||
Local communication software | Local View | ||
Efficiency | |||
Online mode | up to 92% | ||
Environment | |||
Ambient service temperature | 0 °C to +40 °C (15 °C to 25 °C for maximum battery lifetime) | ||
Relative humidity | < 95% non-condensing | ||
Maximum altitude | 1000 m without de-rating | ||
Noise level at 1 m | < 50 dBA | ||
UPS cabinet | |||
Dimensions W x D x H | 145 x 400 x 220 mm | 192 x 460 x 350 mm | |
Weight | 13 kg | 31 kg | 60 kg |
Degree of protection | IP20 | ||
Standards | |||
Safety | IEC/EN 62040-1, AS 62040.1.1, AS 62040.1.2 | ||
EMC | IEC/EN 62040-2, AS 62040.2 | ||
Product certification | CE, RCM (E2376) | ||
ITYS ES – Manual bypass(3) | |||
Sn | 1000 VA | 2000 VA | 3000 VA |
Input | |||
Type of terminals | CBD6 | ||
Wire size | 6 mm2 max | ||
Bypass | |||
Switching positions | 1: UPS – 2: MAINS | ||
Switching time | 6 ms max | ||
Load output | |||
Type of terminals | CBD6 | ||
Wire size | 6 mm2 max | ||
UPS supply output | |||
Type of socket | IEC 320 10 A | IEC 320 16 A | |
Surge arrestors (on request) | |||
Type | “L” in compliance with CEI EN 61643-11 | ||
L/N pulse current | 40 kA (8/20) max | ||
VAC N/GND | 255 V max | ||
VAC L/N | 320 V max |