THÔNG SỐ KỸ THUẬT:
Sn [kVA] | 10 | 15 | 20 |
Pn [kW] | 10 | 15 | 20 |
Parallel configuration | up to 6 units | ||
Input | |||
Rated voltage | 400 V 3ph + N | ||
Voltage tolerances | 240 V to 480 V(1) | ||
Rated frequency | 50/60 Hz ± 10% | ||
Power factor/THDI | > 0.99 / < 2.5% | ||
Output | |||
Power factor | 1 (according to IEC/EN 62040-3) | ||
Rated voltage | 1ph + N: 230 V (can be configured 220/240 V) | ||
Voltage tolerance | static load ±1 % dynamic load in accordance with VFI-SS-111 | ||
Rated frequency | 50 / 60 Hz | ||
Frequency tolerance | ± 2% (configurable for GenSet compatibility) | ||
Total output voltage distortion – linear load | < 1 % | ||
Total output voltage distortion – non-linear load | < 3% | ||
Overload | 125% for 10 minutes, 150% for 1 minute (1) | ||
Crest factor | 3:1 | ||
Bypass | |||
Rated voltage | rated output voltage | ||
Voltage tolerance | ± 15% (configurable with from 10% to 20%) | ||
Rated frequency | 50 / 60 Hz | ||
Frequency tolerance | ± 2% | ||
Efficiency (TÜV SÜD verified) | |||
Online mode @ 50 % of load | up to 96% | ||
Online mode @ 75 % of load | up to 96% | ||
Online mode @ 100 % of load | up to 96% | ||
ECO MODE | up to 98% | ||
Environment | |||
Operating environment temperature | from 0 °C up to 40 °C(1) (from 15 °C to 25 °C for maximum battery life) | ||
Relative humidity | 0% – 95% without condensation | ||
Maximum altitude | 1000 m without derating (max. 3000 m) | ||
Acoustic level at 1 m (ISO 3746) | < 52 dBA | ||
UPS Cabinet | |||
Dimensions W x D x H | 444 x 795 x 800 mm | 444 x 795 x 1000 mm | |
Weight | 190 kg | 195 kg | |
Degree of protection | IP 20 | ||
Colours | RAL 7012 | ||
Standards | |||
Safety | IEC/EN 62040-1, AS 62040.1.1, AS 62040.1.2 | ||
Electromagnetic compatibility (EMC) | IEC/EN 62040-2, AS 62040.2 | ||
Performance | IEC/EN 62040-3, AS 62040.3 | ||
Seismic compliance | On demand according to Uniform Building Code UBC-1997 Zone 4 | ||
Product declaration | CE, RCM (E2376) |