THÔNG SỐ KỸ THUẬT:
| MODEL | HT3110S | HT3115L | HT3120L | HT3140L | ||
| HT3110L | ||||||
| Capacity | 10kVA | 15kVA | 20kVA | 40kVA | ||
| Phase | Three phase in,Single phase out | |||||
| Input Voltage Range | 50%-125%(220VAC/230VAC/240VAC) | |||||
| 100% load@80%-125%; 90% load@70%-80% | ||||||
| 80% load@60%-70%; 65% load@50%-60% | ||||||
| Input PF | ≥0.95 | 0.99 | ||||
| Input Frequency Range | 40Hz-70Hz | |||||
| Output PF | 0.9 | 0.8 | ||||
| Output Voltage | 220V/230V/240V | |||||
| Voltage Regulation | ±1% | |||||
| THDu | ≤1% (full linear load ); ≤5%(none-linear load) | |||||
| Battery Voltage | 192VDC | ±240VDC | ||||
| Battery Type/number | 12V,9Ah*16 | External | External | External | ||
| External | ||||||
| System Efficiency | Normal :93.5%; | Normal:95%; | ||||
| ECO :98%; | ECO:98%; | |||||
| Battery:92% | Battery:95% | |||||
| Noise(1 meter away) | <53dB@<70%load;66dB@>70%load | 65dB @ 100% load, | ||||
| 62dB @ 45% load | ||||||
| Overload Capability | 110%:for 10 min ;130%:for 1min ; | 125% Long run; | ||||
| (Inverter mode) | 150%:for 30 sec (shut down the bypass after 1 min) | 125-130% for 10mins; | ||||
| 130-150% for 1min | ||||||
| Overload Capability | 110%: Shutdown after 10mins; | 125% Long run; | ||||
| (Battery mode) | 125%:Shutdown after 10s; | 125-130% for 10mins; | ||||
| >125%: Shutdown after 1s | 130-150% for 1mins | |||||
| Crest Ratio | 3:01 | |||||
| Display | LED+LCD | |||||
| Interface | Standard:RS232,EPO | Standard: RS232, RS485, USB, Dry Contact | ||||
| Optional: USB, SNMP, Dry contact(Programmable) | Optional: SNMP,AS/400, parallel kit, battery cold start | |||||
| W*D*H(mm) | 250*562*770 | 250*562*650 | 250*562*710 | 600*980*950 | ||
| 250*562*650 | ||||||
| Net Weight(kg) | 69 | 27 | 34 | 170 | ||